Specifications

Rated Voltage 11 KV
Rated Current 100 / 200 / 300 A
Direction of Power Flow Uni-Directional
Tapping Arrangement Linear
Maximum Number of Tap Positions 17
Maximum Step Voltage 300 V
Switching Capacity 60 / 90 KVA
Insulation Level Applied Voltage (KV) Full Wave Lightning Impulse (KV)
A) Tap Changer to Earth 34 110
b) Between Phases 34 110
c) Between First and Last Contacts 25 70
d) Between Any Two Adjacent Contacts 20 50
e) Between Contacts of Change–Over Selector NA NA
Oil Quantity 290 Liters
Weight of OLTC without Oil 370 Kg
Weight of OLTC with Oil 610 Kg