Specifications

Type Reference RCS 36
Applicable Standard IEC 62271-100 / IS 13118
Rated Voltage 33 kV
1 min A.C Power Frequency Withstand Test Level 70 kV
Impulse Withstand 170 kVp
Current Ratings 2000 A
Operating Sequence O – 0.3 sec – CO – 3 min – CO
Maximum Peak Current 66 kA
Short Circuit Current (3 Sec) 26.3 kA
Rated Short Circuit Making Current 66 kA
Rated Short Circuit Breaking Current 26.3 kA
First Pole to Clear Factor 1.2