Technical Specifications

Type Reference RCS 12
Applicable Standard IEC 62271-100 / IS 13118
Rated Voltage 11 kV
1 min A.C Power Frequency Withstand Test Level 28 kV
Impulse Withstand 75 kVp
Current Ratings Up to 1600 A
Operating Sequence O – 0.3 sec – CO – 3 min – CO
Rated Short Circuit Withstand Current 26.3 kA
Rated Peak Withstand Current 66 kA peak
Rated Short Circuit Breaking Current 26.3 kA rms
Rated Short Circuit Making Current 66 kA peak
Rated Single Capacitor Bank Breaking Current 512 A