Specifications

Rated Voltage 11 KV
Rated Current 50 / 65 / 100 A
Direction of Power Flow Bidirectional
Tapping Arrangement Coarse Fine
Maximum Number of Tap Positions 17
Maximum Step Voltage 250 / 300 V
Swiching Capacity 12.5 / 25 KVA
Insulation Level Applied Voltage (KV) Fullwave Lightning Impulse (KV)
A) Tap Changer to Earth 28 75
b) Between Phases 28 75
c) Between First and Last Contacts 8 25
d) Between Any Two Adjacent Contacts 8 25
Oil Quantity NA
Weight of OLTC with Oil 380 Kg