Specifications

Rated Voltage 132
Rated Current 300 A
Direction of Power Flow Bidirectional
Tapping Arrangement Coarse / Fine
Maximum Number of Tap Positions 17
Maximum Step Voltage 1200 V
Switching Capacity 150 kVA
Insulation Level Applied Voltage (KV) Fullwave Lightnining Impulse (KV)
A) Tap Changer to Earth 140 350
B) Between Phases 70 170
C) Between First and Last Contacts 45 200
D) Between Any Two Adjacent Contacts 45 200
Oil Quantity 1364 Liters
Weight of OLTC with Oil 1810 Kg