Specifications

Type Reference KS 12
Applicable Standard IEC 62271-100 / IS 13118
Rated Voltage 11 kV
1 min A.C Withstand Test Level 35 kV
Impulse Withstand 75 kVp
Current Ratings 630 A
Operating Sequence O – 0.3 sec – CO – 3 min – CO
Rated Short Circuit Withstand Current 16 kA for 3 sec
Rated Peak Withstand Current 40 kA peak
Rated Short Circuit Breaking Current 16 kA R.M.S
Rated Short Circuit Making Current 40 kA peak
Degree of Protection IP55