Specifications

Rated Voltage 11 KV
Rated Through-Current 100 A
Direction of Power Flow Uni-Directional
Tapping Arrangement Linear
Maximum Number of Tap Positions 9
Max. Rated Step Voltage 300 V
Switching Capacity 30 KVA
Rated Insulation Level Applied Voltage (KV) Full Wave Lightning Impulse Test (KV)
(a) Tap-Changer to Earth 28 75
(b) Between Phases 28 75
(c) Between First and Last Contact 10 40
(d) Between Any Two Adjacent Contacts 10 40
(e) Between Contacts of Change–Over Selector NA NA
Oil Quantity 45 Liters
Weight of Tap Changer with Oil 110 Kgs